基于逆变型电源暂态电流回代的系统级故障暂态解析
作者:
作者单位:

新能源电力系统国家重点实验室(华北电力大学),北京市102206

摘要:

随着高比例电力电子设备和高比例新能源的接入,未来电力系统需要全时域量保护以应对系统复杂的故障特征。系统级故障暂态分析作为时域量保护的研究基础具有重要意义。鉴于逆变型电源(IIG)的受控特性,系统级故障暂态解析需应对机组输出电流的动态相位换算和多机系统方程高阶求解2个挑战。文中提出一种基于IIG暂态电流回代的系统级故障暂态解析方法。通过分析机组输出功率与端电压相位间的动态关系,实现了IIG暂态电流向统一参考系的动态相位换算;对系统方程进行暂态修正从而避免了高阶运算;在此基础上,网络节点暂态电压可由各机组暂态电流线性求解,进一步得到故障点及全网暂态电流的时域精确解。仿真验证结果表明,所提方法可实现较为精确的系统级故障暂态解析。

关键词:

基金项目:

国家自然科学基金资助项目(51777071)。

通信作者:

作者简介:

贾科(1986—),男,通信作者,博士,教授,主要研究方向:配电网保护和故障定位。E-mail:ke.jia@ncepu.edu.cn
杨彬(1997—),男,博士研究生,主要研究方向:新能源电力系统保护与控制、多换流器故障特性传播。E-mail:544635057@qq.com
刘浅(1998—),男,硕士研究生,主要研究方向:新能源电力系统故障特性分析及故障电流计算。E-mail:wm-lq0428@163.com


Transient Analysis of System-level Fault Based on Transient Current Back-substitution of Inverter Interfaced Generator
Author:
Affiliation:

State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources (North China Electric Power University), Beijing 102206, China

Abstract:

With the integration of high proportion of power electronic equipment and renewable energy, the future power system needs time-domain protection to deal with the complex fault characteristics of the system. System-level fault transient analysis is of great significance as the research basis of time-domain protection. In view of the controlled characteristics of inverter-interfaced generator (IIG), system-level fault transient analysis needs to deal with two challenges: dynamic phase conversion of output current of generation units and solving of high-order multi-generation system equations. A transient analysis method of system-level fault based on transient current back-substitution of IIG is proposed in this paper. By analyzing the dynamic relationship between the output power of generation unit and the terminal voltage phase, the dynamic phase conversion of IIG transient current to unified reference system is realized. The system equation is modified transiently to avoid high-order operation. On this basis, the transient voltage of the network nodes can be solved linearly by the transient current of each generation unit, and the time-domain accurate solution for the transient currents at the fault point and the whole network can be obtained. Simulation results show that the proposed method can achieve more accurate system-level fault transient analysis.

Keywords:

Foundation:
This work is supported by National Natural Science Foundation of China (No. 51777071).
引用本文
[1]贾科,杨彬,刘浅,等.基于逆变型电源暂态电流回代的系统级故障暂态解析[J].电力系统自动化,2022,46(3):113-120. DOI:10.7500/AEPS20201117007.
JIA Ke, YANG Bin, LIU Qian, et al. Transient Analysis of System-level Fault Based on Transient Current Back-substitution of Inverter Interfaced Generator[J]. Automation of Electric Power Systems, 2022, 46(3):113-120. DOI:10.7500/AEPS20201117007.
复制
支撑数据及附录
分享
历史
  • 收稿日期:2020-11-17
  • 最后修改日期:2021-04-23
  • 录用日期:
  • 在线发布日期: 2022-01-27
  • 出版日期: